434 Parameters
98.03 Rr user Defines the rotor resistance R
R
of the motor model.
Resistance value is given at 20 °C (68 °F).
Note: This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000 … 0.50000
p.u.
Rotor resistance in per unit. -
98.04 Lm user Defines the main inductance L
M
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000 …
10.00000 p.u.
Main inductance in per unit. -
98.05 SigmaL user Defines the leakage inductance
L
S
.
Note: This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000 … 1.00000
p.u.
Leakage inductance in per unit. -
98.06 Ld user Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 …
10.00000 p.u
Direct axis inductance in per unit. -
98.07 Lq user Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 …
10.00000 p.u
Quadrature axis inductance in per unit. -
98.08 PM flux user Defines the permanent magnet flux.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 … 2.00000
p.u
Permanent magnet flux in per unit. -
98.09 Rs user SI Defines the stator resistance R
S
of the motor model.
Resistance value is given at 20 °C (68 °F).
0.00000 ohm
0.00000 …
100.00000 ohm
Stator resistance. -
98.10 Rr user SI Defines the rotor resistance R
R
of the motor model.
Resistance value is given at 20 °C (68 °F).
Note: This parameter is valid only for asynchronous motors.
0.00000 ohm
0.00000 …
100.00000 ohm
Rotor resistance. -
98.11 Lm user SI Defines the main inductance L
M
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00 mH
0.00 …100000.00
mH
Main inductance. 1 = 10 mH
98.12 SigmaL user SI Defines the leakage inductance
L
S
.
Note: This parameter is valid only for asynchronous motors.
0.00 mH
0.00 …100000.00
mH
Leakage inductance. 1 = 10 mH