ControlMaster CM15 | Universal process indicator,
1
/
8
DIN | DS/CM15–EN Rev. J 13
Math blocks *
Number:
—8
Operators:
+, –, x, /
Average, Maximum, Minimum
High / Low / Median select
Square root
Multiplexer
Delay timers *
Number:
—2
Programmable:
—Delay
—Duration
Logic equations *
Number:
—8
Elements:
15 per equation
Operators:
OR, AND, NOR, NAND, NOT, EXOR
Custom linearizer *
Number:
—2
Elements:
20 breakpoints
* Indicator fitted with standard function key only
Analog inputs
Universal process inputs
Number:
—1 standard
Typ e :
Voltage
—Current
Resistance (ohms)
—3-Wire RTD
—Thermocouple
Digital volt-free
Digital 24 V
Frequency
Non-universal process inputs
Number:
—1 standard
Typ e :
Voltage
—Current
—Thermocouple *
Digital volt-free
Digital 24 V
Thermocouple types
B, E, J, K, L, N, R, S, T
Resistance thermometer
Pt100
Other linearizations
x, x
3/2
, x
5/2
, custom linearization
Digital filter
Programmable 0 to 60 s
* Only if universal process input is configured as 'Thermocouple'