Electromagnetic Flowmeter
COPA-XE / MAG-XE
Submenu/Parameter Entry Type Comments
from table/numeric
Exit the submenu
The forward direction totalizer value is reset by pressing ENTER.
If the overflow value is > 0, then only reset overflow F is
displayed.
Preset the totalizer (totalizer value can be set)
2nd Display line = present value
Overflow counter, max 250, 1 overflow = pulse totalizer
> 9,999,999 units (display value is reset and overflow counter
incremented by 1).
See forward totalizer
See forward totalizer
See forward overflow counter
Standard = separate totalization of the forward and reverse flow
values, each on its own totalizer.
Difference totalizer = forward and reverse flows are totalized and
displayed as a single value.
from table
Exit the submenu
Selections for the 1st display line: flow rate in %, direct reading
engineering units, mA, totalizer, totalizer forward, totalizer
reverse, TAG-Number or bargraph
See 1st Line
In addition to the values displayed in the 1st line it is possible to
display another value in multiplex operation:
Flow rate in %, engg units, mA, totalizer, totalizer forward,
totalizer reverse, TAG-Number, bargraph or off.
Display alternates every 10 secs.
See 1st line multiplex.
Submenu
Totalizer
C/CE
ENTER
Totalizer V
reset
Totalizer V
4697.00 m3
Overflow V
250
Totalizer R
reset
Totalizer R
625.000 m3
Overflow R
004
Total. Function
Standard
Submenu
Display
C/CE
ENTER
1. Line
Q [%]
2. Line
Totalizer
1. Line multipl.
Q [Bargraph]
2. Line multipl.
off