EasyManua.ls Logo

ABB DPA UPScale ST60 - 12 External Battery Cabinets

ABB DPA UPScale ST60
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modifications reserved
Page 16/26
12 External battery cabinets
S-type = For separate battery
C-type = For common battery
CBAT-UPScale-120
S-type or C-type
CBAT-UPScale200
S-type or C-type
Battery frames
Configuration accommodates: Max.
120 batt. block x 24 Ah/28 Ah
on 8 shelves
3 x 5=15 blocks/shelf
200 batt. blocks x 24 Ah/28 Ah
on 7 shelves
6 x 5=30 blocks/shelf
Battery fuses / max. batt.
strings
terminals :
S-
type
9 / 3
(Terminal 9 x 16/25mm
2
)
15 / 5
(Terminal 15 x 16/25mm
2
)
Battery fuses / max. batt.
strings
terminals :
C-
type
9 / 3
+ Com. connection bar
3 x (2x M8) +PE 2xM8
15 / 5
+ Com. connection bar
3 x (2x M10) +PE 2x M10
Fuse type (very fast-acting) A
3 x 100 A 5 x 100 A
Dimensions (WxHxD) mm
730 x 1975 x 800 1200 x 1975 x 800
Weight with trays and
w/o batteries
kg
290 410
Possible battery configurations
within the battery cabinets
Battery configurations
(1x40)x28Ah / (2x40)x28Ah/
(3x40)x28Ah / (2x50)x28 Ah
Battery configurations
(1x40)x28Ah / (2x40)x28Ah/
(3x40)x28Ah / (4x40)x28Ah/
(5x40)x28Ah / (2x50)x28Ah/
(4x50)x28Ah

Table of Contents