38 S4 D184B122U02
Submenu/
Parameter
Submenu/
Parameter 
Submenu/
Parameter
Selections
Value Range
Comments
AI Channel
Channel setting for the AI-Block. 
When setting the channel, the Unit for the 
channel is also copied to the AI-Block (from 
OUT_SCALE. UNIT_INDEX).
Selection:
TB (Transducer Block) Flow Value
TB Total → F
TB Total ← R
TB Diff Total
TB Flow Value
AI Channel
ENTER TB Total → F
AI Channel
TB Total ← R
AI Channel
TB Diff Total
TOT 1 Channel
Channel setting for the Totalizer-Block.
Only the selection TB Flow Value available. 
When setting the channel, the volume or 
mass Units of the channel are also copied 
from UNIT_TOT 
(Example: m³/h → m³). 
See TOT 1
TB Flow Value
TOT 2 Channel
TB Flow Value
Software Rev. view only
Display of the Communication Software 
Revision level.
Communication: 0
Submenu
Attention 
As soon as a Self Test function is 
initiated, the converter no longer 
operates online, i.e. the outputs no longer 
track the flowrate.
Self check
Memory Test
Test the Memory. Internal FRAM, Ext. 
FRAM and calc. Flash can be interrogat-
ed one after the other using the ENTER-
Function. 
ENTER
Pulse Output
numeric entry This menu is not displayed for PROFIBUS 
PA.
Test the Pulse Output. Enter a value in Hz 
directly. Attention! In the submenu Test, the 
converter no longer operates online, i.e. the 
outputs no longer track the flowrate. 
0 Hz
Current Output
0-20 mA, 4-20 mA
0-10 mA, 2-10 mA
This memory is not displayed for PROFIBUS 
PA.
Test the Current Output. Monitor the dis-
played value at the connection terminals 
with a digital voltmeter or the process instru-
mentation. Entries directly in mA. 
Attention! In the submenu Test, the con-
verter no longer operates online, i.e. the out-
puts no longer track the flowrate. No selec-
tion possible if the Hart Instrument Address 
is other than 0.
4 mA
!