TECHNICAL SPECIFICATIONS
HIPERGUARD MV UPS
USER MANUAL
44
/
103
5. Technical specifications
General product data
Product class 7.2 kV IEC 12kV IEC 15 kV ANSI 24kV IEC
General
Rated Voltage 6-6.6kV 10-11 kV 12.47-13.8kV 20-22kV
Rated apparent power 2500 kVA Single unit
Rated active power 2500 kW
Load power
factor 1.0
Hard parallel
configuration
Up to 10 units
Performance
Efficiency
98% for 50% to 100% loading
96% for 25% to 50% loading
Under
nominal
conditions
Dynamic output
performance
In line with IEC62040-3 VI SS 111
Architecture
ZISC enabled line interactive
Table 5.1: HiPerGuard MV UPS general data
5.1. Utility input
Input
Voltage tolerance ±10 % From nominal voltage
Rated frequency 50 Hz/60 Hz
Frequency tolerance ± 2 % From rated frequency
Displacement power factor
at supply
> 0.96 Under nominal conditions
Battery charging current 0-50%
Grid supplied on top of the load power.
Two setpoints, grid and generator
(default is 10% for both)
Power Distribution system IT, 3-Wire Input
Please contact ABB for other
distribution systems
Current distortion THDi < 3%
Full linear load, under nominal
conditions, operating on power
conditioning mode
Table 5.2: HiPerGuard MV UPS input specifications