EasyManua.ls Logo

ABB LWT300 series - Page 73

ABB LWT300 series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring communications 69
Figure 49 Pulling out the HMI board
HMI board
Communication board
4 On the communication board, set dip switches 3 and 4 to position 1 (see Figure 50). Your LWT
instrument is now ready to be configured via your preferred software tool.
Figure 50 Modbus communication board
ENABLE
1
NV FORMAT
0
PROTOCOL MODE
1
0
SW 3
1
SW 1
0
DISABLE
MODBUS
TM
P/N : 3KXL001060U0400
ENABLE
DISABLE
SW 4
CONFIG / HART-RS485
OPERATE / MODBUS

1 2 3 4
ON
Dip switches
Configuration
HART/RS485
Operation
Modbus
For more information on the configuration setup that you need to start communicating with your
instrument, see “Configuring the LWT300 with a computer” on page 60.
NOTICE
When you are done configuring the instrument remotely via HART, you must toggle the
communication mode back to Operation (switches 3 and 4 to position 0); otherwise the
instrument will not be able to resume sending data when reconnected to the Modbus
network.

Table of Contents

Other manuals for ABB LWT300 series

Related product manuals