MegaFlex 1000 to 1600 UPS User Manual / REV-A
Message Description
INVERTER OFF
The command to switch OFF the Inverter
activated by the Control Panel
or automatically for alarm
presence.
BYPASS UTILITY OK
Bypass Input Utility is again within tolerance (voltage,
frequency and phase).
COMMAND LOAD OFF
Disconnection of the Load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop Operation.
NO BYPASS POWER
With the Load supplied by Automatic Bypass, a Utility
Failure or K6 opening occurred.
MULTIPLE LOAD TRANSFER
2 transfers Inverter- Utility have been detected in a short
time (default 30 sec.).
BYPASS LOCKED
Bypass is not available.
Contactor K6 is open, SSM deactivated.
BYPASS FREE
Bypass is enabled.
Contactor K6 is closed.
LOAD OFF
Push-button “Load Off” on the UPS Control Panel has been
pressed, with “Q1 – External UPS Output Circuit Breaker”
DETOUR ON
The auxiliary contact indicates that “External
Manual
Bypass Breaker” was closed.
DETOUR OFF
The auxiliary contact indicates that “External Manual
Bypass Breaker” was opened.
COMMAND LOAD ON UTILITY
The control unit received a command to transfer the Load
COMMAND LOAD ON INVERTER
The control unit received a command to transfer the Load
End of the overload condition detected with alarm 4570.
INVERTER AND UTILITY SYNCHRONIZED
The voltages of Inverter and Utility Bypass
COMMAND NOT TO SYNCHRONIZE
Command not to synchronize with Utility.
Command to synchronize with Utility.
COMMAND UPS ON
The eBoost operation mode function has been disabled or
the programmed time is expired.
The UPS returns to VFI mode supplying the Load normally
by Inverter.
COMMAND UPS STAND BY
The function eBoost operation mode is enabled and
according to the time program the UPS will run in
eBoost
mode, supplying the Load normally by Utility.
Q1 OPEN
The auxiliary contact indicates that the “Q1 – External UPS
Output Circuit Breaker” was opened.
Q1 CLOSED
The auxiliary contact indicates that the “Q1 –
External UPS
Output Circuit Breaker” was closed.
eBoost ACTIVATION ALLOWED
eBoost control signal has been cleared on the Customer
Interface Board (X1 - 11, 22).
Operating mode depends on
scheduled activation of the
functions.
eBoost ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an eBoost
control signal.
eBoost™ Operation Mode will be temporarily inhibited.
eBoost INHIBITED - LOW LOAD
eBoost™
Operation Mode inhibited due to minimal load not
reached.
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
- No Utility Rectifier or Bypass.
- Battery not fully charged.
- Load is below 10% or above 80%.
Test is postponed for 1 week.