MegaFlex 1000 to 1600 UPS User Manual / REV-A
6.3.3 Messages list
Message Description
WATCHDOG RESET
The microprocessor has detected an incorrect operation:
Transfers the load on Utility and performs a program reset.
The Inverter will restart automatically and will supply the
load.
SENSOR AUTO-CALIBRATION ERROR
The voltage/current reading were not correctly calibrated
when the UPS was switched on.
RECTIFIER UTILITY OK
Rectifier Input Utility is again within the admitted tolerance
(voltage, frequency and phase).
Start of Manual or Automatic Battery Test.
End of Manual or Automatic Battery Test.
MANUAL BOOST CHARGE START
Recharging has been manually activated from the
Panel
, bringing the final load up to the value of the
respective parameter.
AUTOMATIC BOOST CHARGE START
After the Battery has discharged
charge has started to recharge the Battery based on pre-
MANUAL/AUTOMATIC BOOST CHARGE
STOP
The automatic boost charge has finished.
The Battery’s voltage will return to the maintenance value.
A manually
activated boost charge will finish if: it is
manually interrupted, the initial timer setting has expired,
or the Rectifier is not functioning correctly (Alarm 4140).
The Battery voltage will return to the maintenance value.
BOOSTER ON
The Booster is switched ON.
It transfers energy from the Battery to the DC-link.
The Booster is switched Off.
BATTERY CHARGER ON
The Battery charger is switched on and is charging the
Battery.
The Battery charger is switched Off.
GENERATOR ON
Customer Interface (X1 - 11, 22) received a Gen-set ON
signal.
Operating mode depend on setting of Parameters.
GENERATOR OFF
Customer Interface (X1 - 11, 22) received a Gen-set OFF
signal.
Function Bypass enabled depends on setting of Parameter.
INVERTER CANNOT BE TURNED ON
Inverter cannot be switched on because one of the
following conditions is still present:
- Overtemperature
- K7 opening Failure
- Low Battery Voltage
- High Battery Voltage
- Inverter Fuses
- DC Low
- Overload
- EPO (Emergency Power Off)
INVERTER CANNOT BE TURNED OFF
Inverter cannot be switched OFF, because the Load cannot
be switched to Utility
(voltage out of tolerance, not
synchronized, BP blocked).
INVERTER ON
The command to start the Inverter
the Control Panel.