MNS DTR / MNS Service
Konserwacja i części zamienne
Maintena
n
ce
and Spare Parts
5.18.5 Maintenance and Inspection List
Frequency
Install. category
Measured, test and limit values, operating and auxiliary
materials
General visual inspection
(repetitive tests)
Verify ambient conditions
Room temperature 35°C
Air, aggressive gases such as SO
2
, H
2
S etc.
Relative humidity 50 % at 40°C
Auxiliary heating possi-
bly required
Check ventilation system (efficiency)
Air supply to and air discharge from cubicle not obstructed
max. temperature inside the cubicle: 60°C
Touch fronts with hand
surface, check cubicle
if hand-warm spots are
found
Check condition of enclosure / outside paint
Missing parts such as module doors or covers
Ventilation louver dusty / covered
Roof plate contaminated / covered / obstructed / etc.
Fastening of cable compartment doors, side and back panels
Position of withdrawable modules in the cubicle (operating or
isolated position)
Cable / equipment compartment doors closed / open
Completion of the interior
Check filling factor and equipment
Arrangement of modules in accordance with engineering
documents
Contamination, e.g. dust
Cable compartment / cable terminal compartment
Incoming feeder in accordance with documents (busbar / cable
laterally / top / bottom)
Sufficient room / strain relief
Cable routing; bending radii
Personal protection / protective bellows
Check transport connections
Color changes at bolted connections
Check using thermo-
vision exposures
Proper installation of cover in partition wall 3
Contamination or flashover
Formation of cracks or creeping paths
Visual inspection of the condition of the busbar
insulation