MNS DTR / MNS Service
109
Konserwacja i części zamienne
Maintena
n
ce
and Spare Parts
Measured, test & limit values, operating & auxiliary mate-
rials
Insulation molten or even corroded
Screwed connection at electrical equipment
For tightening torque, cf. manufacturer´s instructions
Check controller settings
In accordance with manufacturer´s operating instructions
Power circuit open, i.e.
fused switch discon-
nector removed
Direct connection (incoming and outgoing feeders
with circuit breaker)
Analogous to item 1.3
“Gen. inspection of
switchgear assembly”
Check main switching device
Visual inspection of main connections
Color change at switch main connections
Condition of main and eroded contacts
Check current transformer arrangement
Fastening of transformers
Secondary cable routing
Condition of transformer housings
Check supports at angle and connection sets
Check screwed connections
Mechanical condition of supporting plate
Condition of partitioning (if available)
Formation of creepage paths
Check external connections
Check screwed connections
Check cable strain relief
Cable routing, min. bending radii, edge protection, etc.