108
MNS DTR / MNS Service
Konserwacja i części zamienne
Maintena
n
ce
and Spare Parts
Frequency
Install. category
Measured, test and limit values, operating and auxiliary
materials
Check electrical contacts
Fastening of outgoing cable unit
Position; the outgoing cable unit might be pressed out of
its normal position by strong cable forces
Protective conductor connection
Condition of the roller in the compartment bottom plate
Plug-in, disconnectable, railable technique
Cf. also item no. 1.3:
General inspection
MCC’s and outgoing energy distribution feeders
Compensation modules with and without reactor
Check electrical equipment in every module
Visual inspection of main contacts X01
Condition of short-circuit protection
lubrication not neces-
sary
Signs of overload by
mains
Lubricate contact blades of LV HRC fuses
Check capacitor contactor
Check for contact corrosion
No humming, bouncing or chattering of reactor
Visual inspection of filter circuit reactor
Setpoints see chapter 5.15
Design without reactor: measure all step
currents
3-phase or capacitance values
Limit value: I
B
1,3 x I
n
Design with reactor: measure the terminal
capacitance
Residual voltage after 1 min 50 V
Color change, missing elements
1
Main contact to be checked either according mentioned the time intervals or latest after 100 cycles.