Figure 10: Top view and indication of the minimum clearances for UPS + other cabinets in row.
Table 4: minimum clearances for UPS + other cabinets in row.
PowerWave 33 Series 3 Cabinets 60 / 80 / 100 / 120
UPS + battery cabinets
in row.
A
Back clearance for ventilation
(forced air outlet)
0 mm 100mm
4)
B
Front clearance needed to allow
a correct door opening
1000 mm
C
Maximum door opening angle 115°
D
Top Clearance
(Top clearance is only needed if there is no
side clearance)
400 mm
4)
Battery cabinet requires 100mm clearance for natural ventilation. The UPS does not require any back clearance.