EasyManua.ls Logo

ABB PowerWave 33 Series 3 - Input Characteristics; Current and Distortion Specifications

ABB PowerWave 33 Series 3
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modifications reserved
Page 6/15
ADDITIONAL AND USUAL INFORMATION
Connection 5 wires, 3 phase + N + PE
Cable entry Bottom
Accessibility Frontal only
Air outlet Top
Color Graphite Grey (RAL 7024)
Color code PULVERLACKE NR.4222903402 Ver. 09RCCAT1 ORANGE PEEL
OPTIONS
Battery cabinets
Parallel Kit
SNMP Cards
USB port & Relay card with potential-free contacts (Customer outputs)
Back-feed protection
Single input feed KIT
Sea freight packaging (wooden box)
3 Input characteristics
PowerWave 33 Series 3 60 80 100 120 KW
Rated voltage
(steady-state, r.m.s)
380 / 220
400 / 230
415 / 240
VAC
Tolerance, referred to
400/230V
-10 / +15 at <100% load
-20 / +15 at <80% load,
-30 / +15 at <60% load
%
Frequency, rated
50
Hz
Tolerance, referred to 50Hz
-30 / +40
%
Current (r.m.s), rated
(with battery charged and input
400/230V)
92 122 152 183
A
Current (r.m.s), maximum
(with charging batt. and input
400/230V)
101 134 167 201
A
Total harmonic distortion
(THDi)
≤ 4% at 100% load
%
In-rush current
(A or % of nominal)
< 100% of the rated current
A or %
Power factor
0.99 @ 100% load
Rated short-time withstand
current (I
CW
)
10 for 1.5 seconds
kA, s
AC power distribution system: TN-S, TN-C, TN-C-S, TT
note: in static bypass mode or eco-mode TN-C and TN-C-S can cause PE current to rise above 5% of phase currents.
Phases required
3
Neutral required
yes

Table of Contents

Related product manuals