5.1.1 Customer inputs
The customer input interfaces are standard for each model and are located in the front bottom part of
the unit.
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm
2
Table 8: details of the customer inputs.
X1 / 9 IN
+12Vdc
(Max 200mA load)
X1 / 7 IN
+12Vdc
(Do not remove the factory mounted bridge until an external remote shut down is connected)
+3.3Vdc
(If connected, the battery charger current is batt. temperature dependent)
X1 / 4 GND
GND
(Function on request, to be defined)
X1 / 1
IN
+12Vdc
(NC = Generator ON)
5.1.2 Customer outputs (OPTIONAL USB port & Relay card)
The customer output interfaces are on an optional relay card which goes into slot 2 of the UPS.
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires: 0.5 mm
2
Table 9: details of the customer outputs + USB on the relay card.
Block
Terminal Contact
Signal
On Display Function
X2
X2 / 14
NC
ALARM
NO Alarm Condition
X2 / 13
NO
X2 / 11
NC
Message
(Load on Inverter)
X2 / 8
NC
ALARM
Battery OK
LOAD_ON_INV
Common
X2 / 5
Message
(Load on Mains bypass)
X2 /1
NO
Mains Present
+ USB