Figure 13: bottom front view and connection terminals of PW33 S3 60-80-100-120 kW models.
Table 7: connection terminals overview and tightening torque.
PW33 S3
Model
Input
Rectifier
Input
Bypass
Output Batt (+) N / Batt. (-) PE
Tightening
torque (Nm)
60 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
80 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
100 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
120 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)