EasyManua.ls Logo

ABB PowerWave 33 Series 3 - Load and Efficiency Performance; Bypass Operation and Protection

ABB PowerWave 33 Series 3
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modifications reserved
Page 8/15
Max slew-rate
1
Hz/s
Nominal current (In), r.m.s.
rated:
87 116 145 174
A
Overload on inverter
0.5 @ 150% load; 5 @ 125% load; 20 @ 110% load
min
Fault clearing capability
normal mode and battery
mode (100ms)
2.0 x In 2.0 x In 2.0 x In 2.0 x In
A
Crest factor (Load supported)
3: 1
-
Load power factor, rated
1
-
Displacement
(permissible lead-lag range)
(all range) 0
%, s
AC / AC efficiency in normal mode, linear load:
100% load
95.5
1)
95.5
1)
95.7
1)
95.7
1)
%
75% load
95.8
1)
95.8
1)
96.0
1)
96.0
1)
50% load
96.0
1)
96.0
1)
96.0
1)
96.0
1)
25% load
95.0
1)
95.0
1)
95.0
1)
95.0
1)
Eco-mode efficiency, linear
load
≥ 99.0
%
Bypass - automatic: static switch
Transfer time: inverter
bypass / bypass inverter / in
eco-mode
<1 / <5 / <6
ms
Rated current
87 116 145 174
A
Fault clearing capability
(bypass mode) for 20 ms
10 x In
2)
A
Overload on bypass mode
continuously @ 110% load
0.5 @ 150% load
5 @ 125% load
min
Bypass - maintenance
yes, standard
Bypass protection fuse or
circuit breaker rating
Not included

Table of Contents

Related product manuals