Figure 3: block diagram PowerWave 33 S3 60-120kW
Cable Sections and fuse ratings recommended according to (IEC 60950-1).
Alternatively, local standards to be respected!
Table 4: SINGLE INPUT FEED (CABLE LINKS TO ACHIEVE SINGLE INPUT ARE OPTIONAL)
Rated
output
power
Fuse A
Type:gL or CB
(qty. x A)
Cable A
(qty. x mm
2
)
Cable D
(qty. x mm
2
)
Fuse E
Type:gR or CB
(qty. x A)
Cable E
(qty. x mm
2
)
60
kW
3x100 5x(1x35) 5x(1x35) 2x160 2x(1x50)
80
kW
3x125 5x(1x50) 5x(1x50) 2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160 5x(1x70) 5x(1x70) 2x250
2x(1x120) or 2x(2x50) @ 42-45
batt. blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200 5x(1x95) 5x(1x95) 2x300
2x(1x150) or 2x(2x50) @ 42-45
batt. blocks
2x(1x120) or 2x(2x50) @ 46-50
batt. blocks
Table 5: DUAL INPUT FEED (STANDARD VERSION)
Rated
output
power
Fuse B
Type:gL
or CB
(qty. x A)
Cable B
(qty. x
mm
2
)
Fuse C
Type:gL
or CB
(qty. x A)
Cable C
(qty. x
mm
2
)
Cable D
(qty. x
mm
2
)
Fuse E
Type:gR
or CB
Cable E
(qty. x mm
2
)
60
kW
3x100 5x35 3x100 5x35 5x35 2x160 2x(1x50)
80
kW
3x125 5x50 3x125 5x50 5x50 2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160 5x70 3x160 5x70 5x70 2x250
2x(1x120) or 2x(2x50) @ 42-45
batt. blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200 5x95 3x200 5x95 5x95 2x300
2x(1x150) or 2x(2x50) @ 42-45
batt. blocks
2x(1x120) or 2x(2x50) @ 46-50
batt. blocks