7:1.1 Overview of all accessible settings (different menus) cont.
Description
Display
text
Setting
range
Default
value
Actual
setting
Setting current Setting Ie 9.0...1207A Individual
Time for start ramp Start Ramp 1...30s, 1...120s 10s
Time for stop ramp Stop Ramp 0...30s, 0...120s 0s
Initial voltage for start ramp Init Volt 30...70% 30%
End voltage for stop ramp End Volt 30...70% 30%
Step down voltage Step down 30...100% 100%
Level of the current limit Current Lim 2.0...7.0xle 4.0xle
Selection of kick start Kick Start Yes, No No
Level of kick start Kick Level 50...100% 50%
Time for kick start Kick Time 0.1...1.5s 0.2s
Range for start ramp Start Range 1-30s, 1-120s 1-30s
Range for stop ramp Stop Range 0-30s, 0-120s 0-30s
Overload protection Overload No, Normal, Dual Normal
Overload class OL Class 10A, 10, 20, 30 10
Overload class, Dual type, Start class OL Class S 10A, 10, 20, 30 10
Overload class, Dual type, Run class OL Class R 10A, 10, 20, 30 10
Type of operation for overload protection OL Op
Stop-M, Stop-A, Ind
Stop-M
Locked rotor protection Locked Rotor Yes, No No
Trip level for locked rotor protection Lock R Lev 0.5...8.0xle 4.0xle
Trip time for locked rotor protection Lock R Time 0.2...10s 1.0s
Type of operation for locked rotor protection Lock R Op
Stop-M, Stop-A,
Ind Stop-M
Underload protection Underload Yes, No No
Trip level for underload protection Underl Lev 0.4...0.8xle 0.5xle
Trip time for underload protection Underl Time 1...30s 10s
Type of operation for underload protection Underl Op
Stop-M, Stop-A, Ind
Stop-M
Phase imbalance protection Phase Imb Yes, No No
Trip level for phase imbalance protection Ph Imb Lev 10...80% 80%
Type of operation for imbalance protection Ph Imb Op
Stop-M, Stop-A, Ind
Stop-M
High current protection High I Yes, No No
Type of operation for high current protection High I Op
Stop-M, Stop-A, Ind
Stop-M
Phase reversal protection Phase Rev Yes, No No
Type of operation for phase reversal protection Ph Rev Op
Stop-M, Stop-A, Ind
Stop-M
PTC protection PTC Yes, No No
Type of operation for PTC protection PTC Op Stop-M, Stop-A, Ind Stop-M
Use of external by-pass contactor Ext ByPass Yes, No No
Type of operation, by-pass doesn’t open BP Closed Op Stop-M, Stop A Stop-M
Type of operation, by-pass doesn’t close BP Open Op Stop-M, Stop A Stop-M
High current warning Warn I=High Yes, No No
Trip level for high current warning Wa I=H Lev 0.5...5.0xle 1.2xle
Low current warning Warn I=Low Yes, No No
Trip level for low current warning Wa I=L Lev 0.4...1.0xle 0.8xle
Motor overload warning Warn OL Yes, No No
Trip level for motor overload warning Wa OL Lev 40...99% 90%
Thyristor overload warning Warn SCR OL Yes, No No
Type of operation for phase loss fault Ph Loss Op Stop-M, Stop-A Stop-M
Type of operation for eldbus fault FB Fault Op Stop-M, Stop-A Stop-M
Type of operation for frequency fault Freq F Op Stop-M, Stop-A Stop-M
Type of operation for heatsink overtemp fault HS Temp Op Stop-M, Stop-A Stop-M
Type of operation for shorted thyristor fault SCR SC Op Stop-M, Stop-A Stop-M
Function of programmable input In0 In0
None, Reset,
Enable Jog, DOL,
Start 2, FB-Dis
Reset
Chapter 7
Settings and conguration
Low Voltage Products & Systems 7.5
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201
7