7:1.1 Overview of all accessible settings (different menus) cont.
Description
Display
text
Setting
range
Default
value
Actual
setting
Function of programmable input In1 In1
None, Reset,
Enable Jog, DOL,
Start 3, FB-Dis
Reset
Function of programmable output relay K4 Relay K4 Run, TOR, Event Run
Function of programmable output relay K5 Relay K5 Run, TOR, Event TOR
Function of programmable output relay K6 Relay K6 Run, TOR, Event Event
Function of programmable software relay V7 SW Outp V7 Run, TOR, Event Event
Overload event of relay K4 K4 Overload Yes, No No
Fault event of relay K4 K4 Fault Yes, No No
Shunt fault of relay K4 K4 Shunt Fault Yes, No No
High current event of relay K4 K4 High I Yes, No No
Thyristor overload event of relay K4 K4 SCR OL Yes, No No
Locked rotor event of relay K4 K4 Lock Rot Yes, No No
Underload event of relay K4 K4 Underload Yes, No No
Phase imbalance event of relay K4 K4 Phase Imb Yes, No No
PTC event of relay K4 K4 PTC Yes, No No
Phase reversal event of relay K4 K4 Phase Rev Yes, No No
Warning motor overload event of relay K4 K4 Warn OL Yes, No No
Warning thyristor overload event of relay K4 K4 Wa SCR OL
Yes, No
No
Warning high current event of relay K4 K4 Wa I=High Yes, No No
Warning low current event of relay K4 K4 Wa I=Low Yes, No No
Overload event of relay K5 K5 Overload Yes, No No
Fault event of relay K5 K5 Fault Yes, No No
Shunt fault of relay K5 K5 Shunt Fault Yes, No No
High current event of relay K5 K5 High I Yes, No No
Thyristor overload event of relay K5 K5 SCR OL Yes, No No
Locked rotor event of relay K5 K5 Lock Rot
Yes, No
No
Underload event of relay K5 K5 Underload Yes, No No
Phase imbalance event of relay K5 K5 Phase Imb Yes, No No
PTC event of relay K5 K5 PTC
Yes, No
No
Phase reversal event of relay K5 K5 Phase Rev Yes, No No
Warning motor overload event of relay K5 K5 Warn OL
Yes, No
No
Warning thyristor overload event of relay K5 K5 Wa SCR OL Yes, No No
Warning high current event of relay K5 K5 Wa I=High
Yes, No
No
Warning low current event of relay K5 K5 Wa I=Low Yes, No No
Overload event of relay K6 K6 Overload Yes, No Yes
Fault event of relay K6 K6 Fault Yes, No Yes
Shunt fault of relay K6 K6 Shunt Fault Yes, No Yes
High current event of relay K6 K6 High I Yes, No Yes
Thyristor overload event of relay K6 K6 SCR OL Yes, No No
Locked rotor event of relay K6 K6 Lock Rot Yes, No No
Underload event of relay K6 K6 Underload Yes, No No
Phase imbalance event of relay K6 K6 Phase Imb Yes, No No
PTC event of relay K6 K6 PTC Yes, No No
Phase reversal event of relay K6 K6 Phase Rev Yes, No No
Warning motor overload event of relay K6 K6 Warn OL Yes, No No
Warning thyristor overload event of relay K6 K6 Wa SCR OL Yes, No No
Warning high current event of relay K6 K6 Wa I=High Yes, No No
Warning low current event of relay K6 K6 Wa I=Low Yes, No No
Overload event of relay V7 V7 Overload Yes, No Yes
Fault event of relay V7 V7 Fault Yes, No Yes
High current event of relay V7 V7 High I
Yes, No
Yes
Thyristor overload event of relay V7 V7 SCR OL
Yes, No
No
Locked rotor event of relay V7 V7 Lock Rot
Yes, No
No
Underload event of relay v7 V7 Underload
Yes, No
No
Phase imbalance event of relay V7 V7 Phase Imb
Yes, No
No
Chapter 7
Settings and conguration
7.6 Low Voltage Products & Systems
1SXU 132 021 M0201 ABB Inc. • 888-385-1221 • www.abb-control.com
7