7:1.1 Overview of all accessible settings (different menus) cont.
Description
Display
text
Setting
range
Default
value
Actual
setting
PTC event of relay V7 V7 PTC Yes, No No
Phase reversal event of relay V7 V7 Phase Rev Yes, No No
Warning motor overload event of relay V7 V7 Warn OL Yes, No No
Warning thyristor overload event of relay V7 V7 Wa SCR OL Yes, No No
Warning high current event of relay V7 V7 Wa I=High Yes, No No
Warning low current event of relay V7 V7 Wa I=Low Yes, No No
Control of the softstarter with the eldbus Fieldb Ctrl Yes, No No
Type of eldbus protocol used Fieldb Type AS-Int, Other Other
Fieldbus address Fieldb Addr 0...1000 0
Number of sequences for sequence start No of Seq No, 2, 3 No
1st sequence, time for start ramp Start Ramp 1 1...30s, 1...120s 10s
1st sequence, initial voltage for start ramp Init Volt 1 30...70% 30%
1st sequence, current limit level Curr Lim 1 2.0...7.0xle 4.0xle
1st sequence, setting current 1st Set le 9.0...1207A Individual
2nd sequence, time for start ramp Start Ramp 2 1...30s, 1...120s 10s
2nd sequence, initial voltage for start ramp Init Volt 2 30...70% 30%
2nd sequence, current limit level Curr Lim 2 2.0...7.0xle 4.0xle
2nd sequence, setting current 2st Set le 9.0...1207A Individual
3rd sequence, time for start ramp Start Ramp 3 1...30s, 1...120s 10s
3rd sequence, initial voltage for start ramp Init Volt 3 30...70% 30%
3rd sequence, current limit level Curr Lim 3 2.0...7.0xle 4.0xle
3rd sequence, setting current 3st Set le 9.0...1207A Individual
Language to use on the display Language
US/UK, FI, SE, PT,
NL, IT, FR, ES, DE,
CN, RU, TR
Indiividual
Time for display automatic turn off LCD Auto Off 1...255min 15min
Type of date presentation Date Type ISO, CE, US ISO
Year Date Year 2001...2060 Individual
Month Date Month 1...12 Individual
Day Date Day 1...31 Individual
Hour Time Hour 0...23 Individual
Minutes Time Min 0...59 Individual
Chapter 7
Settings and conguration
Low Voltage Products & Systems 7.7
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201