Chapter 10
Functions
10:55 Startramp,rstsequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Start Ramp1
This parameter makes it possible to set the start ramp time for the rst parameter set.
Parameter text Default value Setting range Description
Start Ramp1 10 s 1...30s, 1...120s First sequence, time for start ramp
10:56Initialvoltage,rstsequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for the rst parameter set.
Parameter text Default value Setting range Description
Init Volt1 30% 30...70% First sequence, initial voltage for start ramp
10:57Currentlimit,rstsequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level for the rst parameter set.
Parameter text Default value Setting range Description
Curr Lim1 4 x Ie 2.0...7.0xle First sequence, current limit
10:58Settingcurrent,rstsequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor current for the rst parameter set.
Parameter text Default value Setting range Description
1st Set Ie Ir
9...1207A divided into 19 over-
lapping ranges
First sequence, current limit
10:59 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time for the second parameter set.
Parameter text Default value Setting range Description
Start Ramp2 10s 1...30s, 1...120s Second sequence, time for start ramp
10:60 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for the second parameter set.
Parameter text Default value Setting range Description
Init Volt2 30% 30...70% Second sequence, initial voltage for start ramp
10.16 Low Voltage Products & Systems
1SXU 132 021 M0201 ABB Inc. • 888-385-1221 • www.abb-control.com