10:61 Current limit, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level for the second parameter set.
Parameter text Default value Setting range Description
Curr Lim2 4 x Ie 2.0...7.0xle Second sequence, current limit
10:62 Setting current, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./2nd Set Ie
This parameter makes it possible to set the rated motor current for the second parameter
set.
Parameter text Default value Setting range Description
2 Set Ie Ir
9...1207A divided into 19
overlapping ranges
Second sequence, current limit
10:63 Start ramp, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Start Ramp3
This parameter makes it possible to set the start ramp time for the third parameter set.
Parameter text Default value Setting range Description
Start Ramp3 10s 1...30s, 1...120s Third sequence, time for start ramp
10:64 Initial voltage, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Init Volt3
This parameter makes it possible to set the initial voltage for the third parameter set.
Parameter text Default value Setting range Description
Init Volt3 30% 30...70% Third sequence, initial voltage for start ramp
10:65 Current limit, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Curr Lim3
This parameter makes it possible to set the current limit level for the third parameter set.
Parameter text Default value Setting range Description
Curr Lim3 4 x Ie 2.0...7.0xle Third sequence, current limit
10:66 Setting current, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq. Start/3rd Seq. Param./3rd Set Ie
This parameter makes it possible to set the rated motor current for the third parameter set.
Parameter text Default value Setting range Description
3rd Set le Ir
9...1207A divided into 19
overlapping ranges
Third sequence, motor rated
current
Chapter 10
Functions
Low Voltage Products & Systems 10.17
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201