7.16 Warnings
The softstarter is equipped with a number of warning
functions to signal malfunctioning or other potential risks,
before asserting the protection or fault. The difference
between a warning and a protection is that a warning
cannot stop the softstarter and a reset of a warning is
not necessary.The warning level and any other additional
information needed to enable the warning can be set by
the user.
A warning will be logged in the event list when it occurs.
Warnings can be Enable or Disable. There is also a
percentage setting were the user can set at which
percentage level the warning shall occur. The percentage
setting is within 10 - 80 %.
Warnings can be set to an Event group by a parameter
option called Out. The Event group can be configured for
relay output to control other devices in an application.
As default, all parameters are set to one Eventgroup.
Warnings are displayed on the HMI, but otherwise they do
not affect the behaviour of the softstarter.
7.16.1 Electronic overload warning
A warning signal will be given if the motor temperature
exceeds the settable warning level, % of max
temperature.
Electronic overload warning
is configured with the following parameters:
Parameter Description Setting range Default value
20.01 EOL level Sets the EOL warning level. 40.0 ... 99.0 % 90.0 %
20.02 EOL out Specifies the Event groups this
warning belongs to.
Event group 0 ... 6 4
23.03 EOL warning Enables EOL warning. Off, On Off
7.16.2 Locked rotor warning
A warning signal will be given if the current exceeds the
settable warning level.
The motor is running stiff. A damaged bearing or a stuck
load could be possible causes. Check the load and the
motor.
Locked rotor warning is configured with the following
parameters:
Parameter Description Setting range Default value
20.04 Locked rotor level Sets the Locked rotor warning level. 0.2 ... 10.0 x I
e
3.0 x I
e
20.05 Locked rotor init time Sets the time delay after top of
ramp when the warning is enabled.
1.0 ... 30.0 s 1.0 s
20.06 Locked rotor out Specifies the Event groups this
warning belongs to.
Eventgroup 0 ... 6 4
20.07 Locked rotor Enables locked rotor warning. Off, On Off
7