10.4 Protection indication shown on screen
For Protections description, see chapter 7.19 Protections group 0-6.
Table 2 Protection indication
Status Possible cause Solution
EOL Protection The motor has been exposed to
an overload condition because the
current over a certain time is too
high. (The load on the motor shaft
is too high)
In Line / Inside Delta
At start
Check starting conditions and EOL settings.
Check and correct the reason for the overload.
Check that Current limit level is not set too low.
Check that the ramp time for start is not too long.
Check that correct overload class is used.
Check that parameter Setting I
e
is correct.
Continuous run
Check the rating of the plate for Ie.
Check operational voltage.
Chose a motor with more power, and
a softstarter rated for higher current.
Check and correct the reason for the
overload.
Check that correct EOL Class is used.
Locked rotor protection The motor is running stiff by some
reason. A damaged bearing or a
stucked load could be possible
causes.
Check the bearings of the motor and load.
Check that the load is not running stiff.
Phase reversal protection The phase sequence is not
correct. Current imbalance
between the phases.
Change the phase sequence on the line side to (L1-
L2-L3).
Restart the motor and check the main currents and
voltage.
Current imbalance protection Current imbalance between the
phases.
Restart the motor and check the main currents and
voltage.
Over voltage protection The main voltage is to high. Check the main voltage.
Under voltage protection The main voltage is to low. Check the main voltage.
Earth fault protection Equipment protection. In a
symmetrical three phase system,
the sum of the instantaneous line
currents is equal to zero. Earth
fault indicates if the sum differs
more than a settable value. This
can indicate a serious condition of
the motor.
Check motor cables.
Check the motor.
Voltage imbalance protection Voltage imbalance between the
phases.
Check the main voltage and restart the motor.
Voltage outputs protection The 24V voltage outputs has been
overloaded or shorted.
Check the connections.
External thermal sensor
- PTC protection
- PT100 protection
The external thermal sensor has
detected a temperature higher
than the trip level in the motor or
PT100.
Check the root cause of the over heating.
Check that the PTC or PT100 circuit is closed and
that the inputs are connected.
Check and correct the reason for the over
temperature.
Wait for the motor to cool sufficiently and restart.
Power factor underload protection The power factor has fallen below
the normal level.
Check and correct the reason for the underload.