External control voltage
The softstarter can, if required, also be controlled with an
external 24 V DC source from a PLC or similar.
Connect the cables according to Figure 31 or Figure 32
depending on which type of control method is used.
WARNING
Terminal 13, 14 ,15, 16 and 17 should be
connected using 24V DC only. Other voltages may
damage the softstarter and the warranty may no
longer be valid.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz K4 K5 K6
Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
Tightening torques and cable dimensions.
31
PSTX
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In1In2 DGND +24V
N
DC
+ -
1SFC132081M0201
In0GND
Figure 31: Holding circuit with external control voltage
(pulse for start is enough)
32
PSTX
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In1In2 DGND +24V
N
STOP
START
N
DC
+ -
1SFC132081M0201
In0
GND
Figure 32: Conventional circuit with external control voltage
(maintained start signal is requierd)
5