5.1.2.5 Programmable output relay - K4,
terminals4,5and6
The output relay gives a signal depending on the selected
function.
Default: Run
See chapter 7 Function settings for programming.
Connect the cables to terminal 4, 5 and 6.
See Figure 38.
Recommended to control line contactor.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3,5
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
5.1.2.6 Programmable output relay - K5,
terminals7,8and9
The output relay gives a signal depending on the selected
function.
Default: Top of ramp
See Chapter 7 Function settings for programming.
Connect the cables to terminal 7, 8 and 9.
See Figure 39.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3,5
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
5.1.2.7 Programmable output relay - K6,
terminals10,11and12
The output relay gives a signal depending on the selected
function.
Default: Event
See chapter 7 Function settings for programming.
Connect the cables to terminal 10, 11 and 12.
See Figure 40.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
38
1SFC132081M0201
Figure 38: ProgrammableoutputrelayK4,terminals4,5and6
39
1SFC132081M0201
Figure 39: ProgrammableoutputrelayK5,terminals7,8and9
40
1SFC132081M0201
Figure 40: ProgrammableoutputrelayK6,terminals10,11and12
5