7.3 Full voltage start
When using the full voltage start the softstarter shall
ensure that the motor accelerates up to full speed as fast
as possible. This is done by providing a full voltage start
in which the motor voltage ramps up to full voltage in ½
seconds.
INFORMATION
Current limit is ignored for full voltage start.
Full voltage start is configured with the following
parameters:
Parameter Description Setting range Default value
02.01 Start mode Set to Full voltage start. Voltage ramp,
Torque ramp,
Full voltage ramp
Voltage ramp
7.4 Direct stop
When using the Direct stop the output voltage to the
motor is 0.
Direct stop is configured with the following
parameters:
Parameter Description Setting range Default value
02.02 Stop mode Set to No ramp. No ramp,
Voltage stop
ramp, Torque
stop ramp
Voltage ramp
7.5 Stand still brake
The Stand still brake breakes the output to the motor,
and can be used during pre-start to assure that the
motor is standing still before Start ramp is initiated. Stand
still brake can also be controlled from a digital I/O or a
fieldbus.
Stand still brake is configured with the following
parameters:
Parameter Description Setting range Default value
02.07 Pre-start function Set to Stand still brake. Off, Motor
heating, Stand
still brake, Jog
forward, Jog
backward
Off
02.08 Pre-start time Set the duration of the pre-start function. 0.0 ... 7200.0 s 10.0 s
07.01 Stand still brake strength Set the Braking strength 10-100%. Choose a
suitable value for the application.
10 ... 100% 50%
7