7.7 Kick start
Kick start function is a function to kick loose the motor
initial friction during a set time and level.
If Kick start is enabled, the start ramp starts directly after
Kick start. See figure 83.
INFORMATION
Current limit function will not work during kick
start.
Kick start is configured with the following parameters:
Parameter Description Setting range Default value
04.01 Kick start Enables a voltage peak at the beginning of the start ramp. On, Off Off
04.02 Kick start level Sets the level of the Kick start in percentage of rated voltage. 50 ... 100 % 70 %
04.03 Kick start time Sets the duration of the Kick start in seconds. 0.20 ... 2.00 s 0.20 s
Figure 83: Kick start
U
Time
Kick Start time
Kick Start level
83