7.9 Motor heating
Motor heating can be used as a pre-start function to
heat the motor before actual start without any rotation to
the motor. It can also be used as an individual function
operated from a digital input or fieldbus.
The softstarter supplies a current to the engine, without
reaching the torque level that starts the engine. This
warms up the engine without starting it.
Motor heating is configured with the following
parameters:
Parameter Description Setting range Default value
02.07 Pre-start function Set to Motor heating. Off, Motor
heating, Stand
still brake, Jog
forward, Jog
backward
Off
02.08 Pre-start time Sets the duration of the pre-start function. 0.0 ... 7200.0 s 10.0 s
06.01 Motor heating capacity Sets the heating power to the motor. Choose a suitable
value for the application.
10 ... 100000 W 10 W