EasyManua.ls Logo

ABB PSTX30 - Page 86

ABB PSTX30
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal Analog output is configured with the following
parameters:
Parameter Description Setting range Default value
10.07 AO reference Sets the Analog output reference. 0-10mA, 0-20mA,
4-20mA, 0-10V
4-20mA
10.08 AO type Sets the Analog output type. Motor current, Mains
voltage, Active power,
Active power, Reactive
power, Apparent power,
Active energy,Reactive
energy, cos fi, Motor
temperature, Thyristor
temperature, Motor
voltage, Mains
frequency, PT100
temperature, PTC
resistance
Motor current [A]
10.09 AO max value Sets the max analog output value. 0,0 ... 1000000 500
10.10 AO min value Sets the min analog output value. 0,0 ... 1000000 0
External Analog output (Extension IO) is configured
with the following parameters:
Description Description Setting range Default value
11.13 1AO0 reference Sets the Analog output reference. 0-10mA, 0-20mA,
4-20mA, 0-10V
4-20mA
11.14 1AO0 type Sets the Analog output type. Motor current, Mains
voltage, Active power,
Active power, Reactive
power, Apparent power,
Active energy,Reactive
energy, cos fi, Motor
temperature, Thyristor
temperature, Motor
voltage, Mains
frequency, PT100
temperature, PTC
resistance
Motor current [A]
11.15 1AO0 max value Sets the max Analog output value. 0,0 ... 1000000 500
11.16 1AO0 min value Sets the min Analog output value. 0,0 ... 1000000 0
7