Reset circuit1)
To parallel R8i modules (if any)2)
OperationStep
Initial status: The drive is in operation and the motor is running.
The user activates emergency stop with the emergency stop button [S61].1
The emergency stop safety relay [A61] de-energizes the digital input on the digital I/O extension
module [A412.X] of the inverter unit. This gives the emergency stop command to the inverter unit.
2
The emergency stop safety relay [A61] de-energizes the timer relay [K61].
The break delay counter of the emergency stop safety relay [A61] starts (user-adjustable delay).
The break delay counter of the timer relay [K61] starts (non-user-adjustable delay).
The inverter unit acknowledges the reception of the emergency stop command by energizing the relay
output (RO1) of the digital I/O extension module [A412.X].
3
The relay output of the extension module [A412.X] energizes the timer relay [K61], resetting its break
delay counter. The relay keeps its delayed break contact closed.
Note: If the drive does not acknowledge the reception of the emergency stop command in 2 seconds,
the main contactor opens and the system is tripped.
The drive decelerates the motor to zero speed in emergency stop deceleration time (user-defined
parameter).
4
The break delay counter of the emergency stop safety relay [A61] trips and the delay contact de-en-
ergizes safety relays [K62.1], [K62.2] and [K62.3].
5
Safety relay [K62.3] de-energizes the XSTO inputs IN1 and IN2 of the inverter control unit [A41]. This
activates the Safe torque off function.
Safety relay [K62.2] de-energizes the DIIL input of the supply control unit [A51]. This gives the
emergency stop command to the supply unit.
Safety relay [K62.1] opens the main contactor/breaker [Qx].
The main contactor/breaker [Qx] disconnects the power supply from the supply unit [T01].
The contact of the safety relay [K62.2] energizes the emergency stop reset button indicator light [S62].6
Normal operation resumes after the user:
7
releases the emergency stop button [S61] to normal (up) position
pushes the emergency stop reset button [S62] for 0.1 3 seconds to reset the emergency stop
circuit
resets the drive (if the drive tripped on a fault).
If the supply unit has an operating switch, it must be switched to position 0 and back to position 1 to
restore the start mode (default).
Option description 23