EasyManua.ls Logo

ABB Q952 - ACS880-17;37 Drives with a Main Contactor (Option +F250)

ABB Q952
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3)
See the recommendation of use CNB/M/11.050 published by the European co-ordination of notified bodies for lower T
1
requirement.
4)
T
1
= 20a is used with high demand mode of operation. T
1
= 1a is used with low demand mode of operation.
5)
12-pulse variant
Note: If T
1
> 1a is needed in low demand mode of operation, SIL 1 / PL c levels are used
and PFD is calculated separately.
ACS880-17/37 drives with a main contactor (option +F250)
T
1
3) 4)
[a]
Mis-
sion
time
[a]
CCFHFTCat.
DC
2)
[%]
PFD
avg
PFH
1)
[1/h]
PLSCSIL /
SIL-
CL
ContactorACS880-17/37
type
20/1206502>906.9E-45.0E-7d32AF145,
AF146 or
AF260
-0105A-3
-0145A-3
-0169A-3
-0206A-3
-0101A-5
-0124A-5
-0156A-5
-0180A-5
20/1206502>901.0E-39.6E-7d32AF370 and
AF16 char-
ging contact-
or
-0293A-3
-0363A-3
-0442A-3
-0505A-3
-0585A-3
-0650A-3
-0260A-5
-0302A-5
-0361A-5
-0414A-5
-0460A-5
-0503A-5
-0174A-7
-0210A-7
-0271A-7
-0330A-7
-0370A-7
-0430A-7
Technical data 47

Table of Contents

Related product manuals