Parameter settings
Contents of this chapter
This chapter contains the parameter settings related to the safety function.
Drive parameter settings
The parameter settings in ACS880 primary control program:
DescriptionDefault valueNameNo.
Activates (and specifies the type of) I/O extension module
1.
FIO-01Module 1 type14.01
Specifies the slot (1…3) on the control unit of the drive into
which the I/O extension module is installed.
Slot 1Module 1 loca-
tion
14.02
Selects whether DIO1 of the extension module is used as a
digital input or output.
InputDIO 1 function14.09
Selects whether DIO2 of the extension module is used as a
digital input or output.
InputDIO 2 function14.14
Selects a drive signal to be connected to relay output RO1.
In this case, the RO1 is energized by the status of DIO2 of
the FIO module (inverted value).
P.14.5.1-RO1 source14.34
Selects the way the motor is stopped when an emergency
stop command is received.
Eme ramp stop
(Off3)
Emergency
stop mode
21.04
Selects the source of the emergency stop signal. In this
case, the source is DIO2 of the FIO module.
P.14.5.1Emergency
stop source
21.05
5
Parameter settings 29