ABB Q952 - Additional Parameter Settings for ACS880-17;37, Frames R8 and R11

ABB Q952
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Additional parameter settings for ACS880-17/37, frames
R8 and R11
The parameters are set at the factory.
The inverter unit parameter settings in the ACS880 primary control program:
parameter 06.40 LSU CW user bit 0 selection is set to Bit 7 (STO) of 06.18 Start inhibit
status word
The supply unit parameter settings in the ACS880 supply control programs:
parameter 121.05 Emergency stop source is set to Bit12- (user bit 0, inverted value) of
106.01 Main control word
Parameter settings 31