7.4.4 Self supervision HMI data
Table 18: Signals from the General menu in the diagnostics tree.
Indicated result Possible reason Proposed action
InternFail OK No problem detected. None.
InternFail Fail A failure has occurred. Check the rest of the indicated results to find
the fault.
InternWarning OK No problem detected. None.
InternWarning Warning A warning has been
issued.
Check the rest of the indicated results to find
the fault.
NUM-modFail OK No problem detected. None.
NUM-modFail Fail The main processing
module has failed.
Contact your ABB representative for service.
NUM-modWarning OK No problem detected. None.
NUM-modWarning
Warning
There is a problem with:
• the real time clock.
• the time
synchronization.
Set the clock.
If the problem persists, contact your ABB
representative for service.
ADC-module OK No problem detected. None.
ADC-module Fail The AD conversion
module has failed.
Contact your ABB representative for service.
CANP 9 BIM1 Fail IO module has failed. Check that the IO module has been
configured and connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
RealTimeClock OK No problem detected. None.
RealTimeClock Warning The real time clock has
been reset.
Set the clock.
TimeSync OK No problem detected. None.
TimeSync Warning No time synchronization. Check the synchronization source for
problems.
If the problem persists, contact your ABB
representative for service.
7.5 REX060 start up sequence
When the injection unit REX060 is energized, the ABB logotype is shown
followed by current REX060 revision status. When the start up sequence is
completed, the main menu (normal display content) is shown. The duration of the
start up sequence is a few seconds.