IEC11000037-1-en.vsd
IEC11000037 V1 EN
Figure 19: Measure and drilling plan
REX061 shall be mounted close to the generator in order to limit the exposure of
the field circuit. Alternatively it can be located in the excitation cubicle.
5.3.8.2 Shunt resistor unit REX062
X1
IEC11000038-1-en.vsd
IEC11000038 V1 EN
Figure 20: Shunt resistor unit REX062
1MRK 502 029-UEN A Section 5
Installing the IED
43
Installation and commissioning manual