Current/voltage
configuration
(50/60 Hz)
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220
V
110-220
V
110-220
V
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220
V
110-220
V
110-220
V
5I, 1A+4I, 5A+3U 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220
V
110-220
V
110-220
V
7I+5U, 1A 1A 1A 1A 1A 1A 1A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
7I+5U, 5A 5A 5A 5A 5A 5A 5A 5A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
6I, 5A+1I, 1A+5U 5A 5A 5A 5A 5A 5A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
3I, 5A+4I, 1A+5U 5A 5A 5A 1A 1A 1A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
3IM, 1A+4IP, 1A+5U 1AM
*)
1AM
*)
1AM
*)
1A 1A 1A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
3IM, 5A+4IP, 5A+5U 5AM
*)
5AM
*)
5AM
*)
5A 5A 5A 5A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
6I+6U, 1A 1A 1A 1A 1A 1A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
6I+6U, 5A 5A 5A 5A 5A 5A 5A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
3I, 5A+3I, 1A+6U 5 A 5 A 5 A 1A 1A 1A 110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
110-220
V
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
*) Metering
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.
Section 5 1MRK 502 029-UEN A
Installing the IED
52
Installation and commissioning manual