If the IED is equipped with a test-switch of type RTXP 24, COMBIFLEX wires
with 20 A sockets, 1.5mm² (AWG16) conductor area must be used to connect the
auxiliary power.
Procedure
1. Connect signals to the female connector
All wiring to the female connector should be done before it is plugged into
the male part and screwed to the case. The conductors can be of rigid type
(solid, stranded) or of flexible type.
The female connectors accept conductors with a cross section area of 0.2-2.5
mm
2
(AWG 24-14). If two conductors are used in the same terminal, the
maximum permissible cross section area is 0.2-1 mm
2
(AWG 24-18).
If two conductors, each with area 1.5 mm
2
(AWG 16) need to be connected to
the same terminal, a ferrule must be used, see figure
36. This ferrule, is
applied with the by Phoenix recommended crimping tool.The fastening screw
shall be tightened with a torque of 0.4 Nm (This torque applies to all binary
connectors).
2. Plug the female connector to the corresponding back-side mounted male
connector
3. Lock the female connector by fastening the lock screws
IEC02000742 V1 EN
Figure 34: A female connector
IEC04000167 V1 EN
Figure 35: Board with male connectors
Section 5 1MRK 502 029-UEN A
Installing the IED
62
Installation and commissioning manual