Section 3 1MRS240173-IB B
0x registers
16 REF615R
DPU2000R Modbus Point List Mitigation Manual
115 Latching Output 3
(LO3)
115 LD0.SRGAPC1.Q3.stVal
116 Latching Output 4
(LO4)
116 LD0.SRGAPC1.Q4.stVal
117 Latching Output 5
(LO5)
117 LD0.SRGAPC1.Q5.stVal
118 Latching Output 6
(LO6)
118 LD0.SRGAPC1.Q6.stVal
119 Latching Output 7
(LO7)
119 LD0.SRGAPC1.Q7.stVal
120 Latching Output 8 (LO8)) 120 LD0.SRGAPC1.Q8.stVal
121 ON Tagging Relay ON (TR ON) N/A in REF615R
122 OFF Tagging Relay OFF (TR OFF) N/A in REF615R
123 TAG Tagging Relay TAGGED (TR TAG) N/A in REF615R
124 59 3 Phase Overvoltage (3PH 59) N/A in REF615R
125 59 3 Phase Overvoltage Latched
(3PH 59-1 latch)
N/A in REF615R
126 Negative Sequence Overvoltage (47) 126 LD0.NSPTOV1.Op.general
127 Negative Sequence Overvoltage Latched (47
latch)
See Section 7.1.6 for
example or explanation
128 Instantaneous 3 phase Over-current alarm
disabled (50-3D)
See Section 7.1.7 for
example or explanation
129 Phase Distance Zone 1 (21P-1) N/A in REF615R
130 Phase Distance Zone 1 Latched (21P-1 latch) N/A in REF615R
131 Phase Distance Zone 2 (21P-2) N/A in REF615R
132 Phase Distance Zone 2 Latched (21P-2 latch) N/A in REF615R
133 Phase Distance Zone 3 (21P-3) N/A in REF615R
134 Phase Distance Zone 3 Latched (21P-3 latch) N/A in REF615R
135 Phase Distance Zone 4 (21P-4) N/A in REF615R
136 Phase Distance Zone 4 Latched (21P-4 latch) N/A in REF615R
137 Control Button Status (C1 (Control Button 1)) 137 LD0.SPCGGIO1.SPCSO1.stVal
138 Control Button Status (C2 (Control Button 2)) 138 LD0.SPCGGIO1.SPCSO2.stVal
139 Control Button Status (C3 (Control Button 3)) 139 LD0.SPCGGIO1.SPCSO3.stVal
140 Control Button Status (C4 (Control Button 4)) 140 LD0.SPCGGIO1.SPCSO4.stVal
141 Control Button Status (C5 (Control Button 5)) 141 LD0.SPCGGIO1.SPCSO5.stVal
142 Control Button Status (C6 (Control Button 6)) 142 LD0.SPCGGIO1.SPCSO6.stVal
143 Trip Target
(TripT)
143 LD0.LEDPTRC1.Op.general
144 Neutral Target Alarm (NTA) 144 LD0.LEDGGIO1.ISCSO4.stVal
145 Time Target
(TimeT)
145 LD0.LEDGGIO1.ISCSO5.stVal
146 Instantaneous Target (InstT) 146 LD0.LEDGGIO1.ISCSO6.stVal
147 Negative Sequence Target (NegSeqT) 147 LD0.LEDGGIO1.ISCSO7.stVal
148 Frequency Target (FreqT) 148 LD0.LEDGGIO1.ISCSO8.stVal
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R
Modbus points mapping