1MRS240173-IB B Section 3
0x registers
REF615R 17
DPU2000R Modbus Point List Mitigation Manual
149 Directional Target
(DirT)
149 LD0.LEDGGIO1.ISCSO9.stVal
150 Voltage Target
(VoltT)
150 LD0.LEDGGIO1.ISCSO10.stVal
151 Distance Target
(DistT)
151 LD0.LEDGGIO1.ISCSO11.stVal
152 Sensitive Earth Fault Target (SEFT) N/A in REF615R
153 User Logical Output 10 Status (ULO10) N/A in REF615R
154 User Logical Output 11 Status (ULO11) N/A in REF615R
155 User Logical Output 12 Status (ULO12) N/A in REF615R
156 User Logical Output 13 Status (ULO13) N/A in REF615R
157 User Logical Output 14 Status (ULO14) N/A in REF615R
158 User Logical Output 15 Status (ULO15) N/A in REF615R
159 User Logical Output 16 Status (ULO16) N/A in REF615R
160 Live Bus Live Line Status (LBLL) 160 LD0.SECRSYN1.LLLBInd.stVal
161 Live Bus Dead Line Status (LBDL) 161 LD0.SECRSYN1.DLLBInd.stVal
162 Dead Bus Live Line Status (DBLL) 162 LD0.SECRSYN1.LLDBInd.stVal
163 Dead Bus Dead Line Status (DBDL) 163 LD0.SECRSYN1.DLDBInd.stVal
164 Negative Sequence Time Over-current Trip
Alarm (46A)
164 LD0.NSPTOC2.Op.general
165 Negative Sequence Time Over-current Trip
Alarm (46A latch)
See Section 7.1.6 for
example or explanation
166 Local Remote Disabled Status (REMOTE D) 166 CTRL.LLN0.LocRem.stVal
167 Setting Active Primary Settings are Active
(Prim)
167 LD0.LLN0.Act1SG.stVal
168 Alternate Setting Group 1 is Active (ALT1) 168 LD0.LLN0.Act2SG.stVal
169 Alternate Setting Group 2 is Active (ALT2) 169 LD0.LLN0.Act3SG.stVal
170 TEST SHIFTER A is in Position 1 (SHIFTA-1) N/A in REF615R
171 TEST SHIFTER A is in Position 2 (SHIFTA-2) N/A in REF615R
172 TEST SHIFTER A is in Position 3 (SHIFTA-3) N/A in REF615R
173 TEST SHIFTER A is in Position 4 (SHIFTA-4) N/A in REF615R
174 TEST SHIFTER B is in Position 1 (SHIFTB-1) N/A in REF615R
175 TEST SHIFTER B is in Position 2 (SHIFTB-2) N/A in REF615R
176 TEST SHIFTER B is in Position 3 (SHIFTB-3) N/A in REF615R
177 TEST SHIFTER B is in Position 4 (SHIFTB-4) N/A in REF615R
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R
Modbus points mapping
PATA, PBTA, PCTA are mapped to different coil addresses in REF615R
with those in DPU2000R.