2.3.2 General device data
Table 4: General device data
Object type Addr IEC 61850 name SA name Description Values
CTRL.LLN0
1 10 Loc.stVal Local state 1=Local
LD0.LNN0
1 13 .SetSeld.stVal Settings reserved 1=Reserved
1 14 .SetChg.stVal Settings changed 1=Changed
DR.RDRE1
1 12 .RcdMade.stVal DR recording made 1=Made
LD0.GSEGGIO1
1 15 .Alm.stVal Goose Alarm 1=Alarm
LD0.LLN0
1 20 .PhyHealth1.stVal (Wrn) Warning (one bit) 1=Warning
1 30 .PhyHealth2.stVal (IRF) IRF (one bit) 1=IRF
LD0.LLN0
1 40001 .ActSG.stVal.SG1 Setting group 1 in use 1=In Use
1 40002 .ActSG.stVal.SG2 Setting group 2 in use 1=In Use
1 40003 .ActSG.stVal.SG3 Setting group 2 in use 1=In Use
1 40004 .ActSG.stVal.SG4 Setting group 3 in use 1=In Use
1 40005 .ActSG.stVal.SG5 Setting group 4 in use 1=In Use
1 40006 .ActSG.stVal.SG6 Setting group 5 in use 1=In Use
2.3.3 LD0.FPHLPTOC1 FA - Phase overcurrent protection, low
stage (1)
Table 5: LD0.FPHLPTOC1 FA - Phase overcurrent protection, low stage (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.FPHLPTOC1
1 1010 .Str.general START General start 1=Start
1 1011 .Str.phsA phase A start 1=Start
1 1012 .Str.phsB phase B start 1=Start
1 1013 .Str.phsC phase C start 1=Start
1 1006 .Op.general OPERATE General operate 1=Operate
1 1007 .Op.phsA phase A operate 1=Operate
1 1008 .Op.phsB phase B operate 1=Operate
1 1009 .Op.phsC phase C operate 1=Operate
Section 2 1MRS757824 C
IEC 60850-5-101/104 data mappings
16 Recloser Protection and Control RER615
Point List Manual