2.3.51 LD0.PHQVVR1 PQ - Voltage variation signals (1)
Table 53: LD0.PHQVVR1 PQ - Voltage variation signals (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.PH1QVVR1
1 3092 .VarStrGen.stVal Variation event detected 1=Detected
1 3088 .VarEnd.stVal Variation event ended 1=Ended
1 3089 .SwlOp.stVal Swell event detected 1=Detected
1 3090 .DipOp.stVal Dip event detected 1=Detected
1 3091 .IntrOp.stVal Interruption event detected
2.3.52 LD0.VSQVUB1 PQ - Voltage unbalance detection (1)
Table 54: LD0.VSQVUB1 PQ - Voltage unbalance detection (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.VSQVUB1
1 3093 .VarStr.stVal Event start 1=Start
1 3094 .HiPctVUnb.stVal Unbalance exceeds limit 1=Exceeds
2.3.53 CTRL.DCSXSWI1 Disconnector position indication (1)
Table 55: CTRL.DCSXSWI1 Disconnector position indication (1)
Object type
Addr IEC 61850 name SA name Description Values
CTRL.DCSXSWI1
2 7020 .Pos.stVal POSITION Interm.=0; Off=1; On=2; Bad=3 0...3
2.3.54 CTRL.DCSXSWI1 Disconnector position indication (2)
Table 56: CTRL.DCSXSWI1 Disconnector position indication (2)
Object type
Addr IEC 61850 name SA name Description Values
CTRL.DCSXSWI2
2 7030 .Pos.stVal POSITION Interm.=0; Off=1; On=2; Bad=3 0...3
2.3.55 CTRL.ESSXSWI1 Earthing switch indication (1)
Table 57: CTRL.ESSXSWI1 Earthing switch indication (1)
Object type
Addr IEC 61850 name SA name Description Values
CTRL.ESSXSWI1
2 7050 .Pos.stVal POSITION Interm.=0; Off=1; On=2; Bad=3 0...3
Section 2 1MRS757824 C
IEC 60850-5-101/104 data mappings
30 Recloser Protection and Control RER615
Point List Manual