Object type Addr IEC 61850 name SA name Description Values
20 12037 .VoltsA.mag PhsA voltage 0...5.00 [xUn]
20 12038 .VoltsB.mag PhsB voltage 0...5.00 [xUn]
20 12039 .VoltsC.mag PhsC voltage 0...5.00 [xUn]
20 12040 .VoltsAB.mag PhsAB voltage 0...5.00 [xUn]
20 12041 .VoltsBC.mag PhsBC voltage 0...5.00 [xUn]
20 12042 .VoltsCA.mag PhsCA voltage 0...5.00 [xUn]
20 12044 .VZroSeq.mag Zero seq. voltage 0...5.00 [xUn]
20 12045 .VPsSeq.mag Positive seq. voltage 0...5.00 [xUn]
20 12046 .VNgSeq.mag Negative seq. voltage 0...5.00 [xUn]
20 12060 .VoltsAb.mag PhsA voltage (b) 0...5.00 [xUn]
20 12061 .VoltsBb.mag PhsB voltage (b) 0...5.00 [xUn]
20 12062 .VoltsCb.mag PhsC voltage (b) 0...5.00 [xUn]
20 12063 .VoltsABb.mag PhsAB voltage (b) 0...5.00 [xUn]
20 12064 .VoltsBCb.mag PhsBC voltage (b) 0...5.00 [xUn]
20 12065 .VoltsCAb.mag PhsCA voltage (b) 0...5.00 [xUn]
20 12066 .VZroSeqb.mag Zero seq. voltage (b) 0...5.00 [xUn]
20 12067 .VPsSeqb.mag Positive seq. voltage (b) 0...5.00 [xUn]
20 12068 .VNgSeqb.mag Negative seq. voltage (b) 0...5.00 [xUn]
20 12047 .MaxTmpRl.mag Relative temperature 0...99.99
20 12048 .PDNS1MxRat.mag PDNSPTOC1 ratio I2/I1 0...999.99 [%]
20 12050 .DifAngBC.mag PhsB-C angle -/+ 180.0 [Deg]
20 12051 .DifAngCA.mag PhsC-A angle -/+ 180.0 [Deg]
20 12052 .DifAngAB.mag PhsA-B angle -/+ 180.0 [Deg]
20 12053 .Hz.mag Frequency 30...80.00 [Hz]
20 12054 .HzS.mag Frequency gradient -/+10.00 [Hz/s]
20 12069 .PPLoopRis.mag Fault loop resistance -/+ 100.00 [Ohm]
20 12070 .PPLoopReac.mag Fault loop reactance -/+ 100.00 [Ohm]
20 12071 .CBClrTm Breaker clear time 0...3.000 [s]
2.5 Integrated totals
2.5.1 Supported ASDU types
The Object type column contains an internal type identification for the data objects.
Internal object types in turn can be configured into different IEC 60870-5-101/104
ASDU data types.
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 45