2.3.76 LD0.XGGIO110 Physical I/O states
Table 78: LD0.XGGIO110 Physical I/O states
Object type Addr IEC 61850 name SA name Description Values
LD0.XGGIO110
1 5020 .Ind1.stVal Input 1 state 0/1=Off/On
1 5021 .Ind2.stVal Input 2 state 0/1=Off/On
1 5022 .Ind3.stVal Input 3 state 0/1=Off/On
1 5023 .Ind4.stVal Input 4 state 0/1=Off/On
1 5024 .Ind5.stVal Input 5 state 0/1=Off/On
1 5025 .Ind6.stVal Input 6 state 0/1=Off/On
1 5026 .Ind7.stVal Input 7 state 0/1=Off/On
1 5027 .Ind8.stVal Input 8 state 0/1=Off/On
1 5030 .SPCSO01.stVal Output 1 state 0/1=Off/On
1 5031 .SPCSO02.stVal Output 2 state 0/1=Off/On
1 5032 .SPCSO03.stVal Output 3 state 0/1=Off/On
1 5033 .SPCSO04.stVal Output 4 state 0/1=Off/On
2.3.77 LD0.XGGIO120 Physical I/O states
Table 79: LD0.XGGIO120 Physical I/O states
Object type
Addr IEC 61850 name SA name Description Values
LD0.XGGIO120
1 5010 .Ind1.stVal Input 1 state 0/1=Off/On
1 5011 .Ind2.stVal Input 2 state 0/1=Off/On
1 5012 .Ind3.stVal Input 3 state 0/1=Off/On
1 5013 .Ind4.stVal Input 4 state 0/1=Off/On
2.3.78 LD0.LEDPTRC1 Global protection signals
Table 80: LD0.LEDPTRC1 Global protection signals
Object type
Addr IEC 61850 name SA name Description Values
LD0.LEDPTRC1 Global protection signals
1 40 .Str.general - General Start 1=Start
1 41 .Str.phsA - phsA Start 1=Start
1 42 .Str.phsB - phsB Start 1=Start
1 43 .Str.phsC - phsC Start 1=Start
1 44 .Str.neut - neut Start 1=Start
1 45 .Op.general - General Operate 1=Operate
1 46 .Op.phsA - phsA Operate 1=Operate
Table continues on next page