2.3.4 LD0.PHHPTOC1 Phase overcurrent protection, high stage
(1)
Table 6: LD0.PHHPTOC1 Phase overcurrent protection, high stage (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.PHHPTOC1
1 979 .Str.general START General start 1=Start
1 980 .Str.phsA phase A start 1=Start
1 981 .Str.phsB phase B start 1=Start
1 982 .Str.phsC phase C start 1=Start
1 975 .Op.general OPERATE General operate 1=Operate
1 976 .Op.phsA phase A operate 1=Operate
1 977 .Op.phsB phase B operate 1=Operate
1 978 .Op.phsC phase C operate 1=Operate
2.3.5 LD0.PHIPTOC1 Phase overcurrent protection,
instantaneous stage (1)
Table 7: LD0.PHIPTOC1 Phase overcurrent protection, instantaneous stage (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.PHIPTOC1
1 995 .Str.general START General start 1=Start
1 996 .Str.phsA phase A start 1=Start
1 997 .Str.phsB phase B start 1=Start
1 998 .Str.phsC phase C start 1=Start
1 991 .Op.general OPERATE General operate 1=Operate
1 992 .Op.phsA phase A operate 1=Operate
1 993 .Op.phsB phase B operate 1=Operate
1 994 .Op.phsC phase C operate 1=Operate
2.3.6 LD0.FDPHLPDOC1 FA - Directional phase overcurrent
protection, low stage (1)
Table 8: LD0.FDPHLPDOC1 FA - Directional phase overcurrent protection, low stage (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.FDPHLPTOC1
1 844 .Str.general START General start 1=Start
1 845 .Str.phsA phase A start 1=Start
1 846 .Str.phsB phase B start 1=Start
1 847 .Str.phsC phase C start 1=Start
Table continues on next page
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 17