Table 66: ULTVTR Output signals
Name Type Description
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
3.14.3.5 Settings
Table 67: ULTVTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Primary voltage 0.100...440.000 kV 0.001 20.000 Primary rated voltage
Secondary voltage 60...210 V 1 100 Secondary rated voltage
VT connection
1=Wye
2=Delta
3=U12
4=UL1
2=Delta Voltage transducer measure-
ment connection
Amplitude Corr A 0.9000 ... 1.1000 0.0001 1.0000 Phase A Voltage phasor magni-
tude correction of an external
voltage transformer
Amplitude Corr B 0.9000 ... 1.1000 0.0001 1.0000 Phase B Voltage phasor magni-
tude correction of an external
voltage transformer
Amplitude Corr C 0.9000 ... 1.1000 0.0001 1.0000 Phase C Voltage phasor magni-
tude correction of an external
voltage transformer
Division ratio 1000 ... 20000 1 10000 Voltage sensor division ratio
Voltage input type
1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A Voltage phasor angle
correction of an external volt-
age transformer
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B Voltage phasor angle
correction of an external volt-
age transformer
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C Voltage phasor angle
correction of an external volt-
age transformer
3.14.3.6 Monitored data
Monitored data is available in three locations.
Monitoring> I/O status> Analog inputs
Monitoring> IED status> SMV traffic
Monitoring> IED status> SMV accuracy
3.14.4 RESTVTR function block
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
117