EasyManua.ls Logo

ABB Relion RER615 - Monitored Data; Technical Revision History

ABB Relion RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values
(Range)
Unit Step Default Description
3=Both
4=Level trig-
ger off
Storage mode
0=Waveform
1=Trend / cy-
cle
1 0 Storage mode
for the binary
channel
Channel id
text
0 to 64 char-
acters, alpha-
numeric
DR binary
channel X
Identification
text for the
analog chan-
nel used in
the COM-
TRADE format
Table 644: RDRE Control data
Parameter Values
(Range)
Unit Step Default Description
Trig recording
0=Cancel
1=Trig
Trigger the
disturbance
recording
Clear record-
ings
0=Cancel
1=Trig
Clear all re-
cordings cur-
rently in
memory
8.2.6 Monitored data
8.2.6.1 Monitored data
Table 645: RDRE Monitored data
Parameter Values (Range) Unit Step Default Description
Number of record-
ings
0...100 Number of record-
ings currently in
memory
Rem. amount of
rec.
0...100 Remaining amount
of recordings that
fit into the availa-
ble recording mem-
ory, when current
settings are used
Rec. memory used 0...100 % Storage mode for
the binary channel
Time to trigger 0...604 800 s Time remaining to
the next periodic
triggering
1MRS758755 C Measurement functions
REC615 & RER615
Technical Manual
625

Table of Contents

Other manuals for ABB Relion RER615