Technical revision history
Table 142: RS Technical revision history
Technical revision Change
L The name of the function has been changed
from SR to RS.
3.17.2 Minimum pulse timer
3.17.2.1 Minimum pulse timer TPGAPC
Function block
Figure 77: Function block
Functionality
The Minimum pulse timer function TPGAPC contains two independent timers. The
function has a settable pulse length (in milliseconds). The timers are used for
setting the minimum pulse length for example, the signal outputs. Once the input is
activated, the output is set for a specific duration using the
Pulse time
setting. Both
timers use the same setting parameter.
Figure 78: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
Table 143: TPGAPC Input signals
Name
Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
145