3.17.10.1 Function block
AI1_VALUE
AI2_VALUE AO2_VALUE
AI3_VALUE
AI4_VALUE
AO3_VALUE
AO4_VALUE
AO1_VALUE
SCA4GAPC
Figure 95: Function block
3.17.10.2 Functionality
The analog value scaling function SCA4GAPC is used for scaling the analog value. It
allows creating events from analog values.
The analog value received via the AIn_VALUE input is scaled with the
Scale ratio n
setting. The scaled value is available on the AOn_VALUE output.
Analog input range is from –10000.0 to 10000.0.
Analog output range is from –2000000.0 to 2000000.0.
If the value of the AIn_VALUE input exceeds the analog input range,
AOn_VALUE is set to 0.0.
If the result of AIn_VALUE multiplied by the Scale ratio n setting exceeds
the analog output range, AOn_VALUE shows the minimum or maximum
value, according to analog value range.
3.17.10.3 Signals
Table 179: SCA4GAPC Input signals
Name Type Default Description
AI1_VALUE FLOAT32 0.0 Analog input value of
channel 1
AI2_VALUE FLOAT32 0.0 Analog input value of
channel 2
AI3_VALUE FLOAT32 0.0 Analog input value of
channel 3
AI4_VALUE FLOAT32 0.0 Analog input value of
channel 4
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
163